Edit Approved Items

Edit your approved study bank (583 total items)

Showing 301-325 of 583 items

Approved Page 0

Wireless fire detection systems must:

A. Use any consumer wifi
B. Be listed for the application and maintain supervision and power requirements ✓
C. Use unlisted batteries
D. Avoid supervision

Be listed for the application and maintain supervision and power requirements

Definition: Wireless components must be listed and maintain supervision, tamper, and power performance.

Approved Page 0

Multi criteria detectors combine sensors to:

A. Increase nuisance alarms
B. Improve detection reliability and reduce non fire alarms ✓
C. Replace manual stations
D. Eliminate maintenance

Improve detection reliability and reduce non fire alarms

Definition: Using multiple sensing technologies can better discriminate fire from non fire phenomena.

Approved Page 0

For elevator lobbies, detector placement should consider:

A. Distance from doors and air movement ✓
B. Only ceiling color
C. Only floor covering
D. Only light fixtures

Distance from doors and air movement

Definition: Door piston winds and air currents can move smoke; avoid dead air and drafts to ensure timely detection.

Approved Page 0

Class A initiating loops are preferred over Class B when:

A. Shortest wiring is required
B. Increased survivability past a single open is desired ✓
C. No supervision is needed
D. Voltage is unknown

Increased survivability past a single open is desired

Definition: Class A loops maintain operation beyond a single open by providing a return path.

Approved Page 0

Class B circuits require what at the end of line?

A. Nothing
B. A capacitor
C. An "EOL" resistor at the last device ✓
D. A diode

An "EOL" resistor at the last device

Definition: The end of line resistor supervises the entire run for opens and grounds.

Approved Page 0

Ground faults should:

A. Be ignored during alarms
B. Annunciate and be located for repair ✓
C. Be masked to prevent nuisance
D. Only be logged in history

Annunciate and be located for repair

Definition: Grounds can hide other faults; prompt indication and repair are required.

Approved Page 0

"NAC" voltage drop increases primarily with:

A. Shorter wire lengths
B. Lower current
C. Higher current and longer runs ✓
D. Better splices

Higher current and longer runs

Definition: Voltage drop equals current times resistance; more load and distance increase drop.

Approved Page 0

To reduce "NAC" voltage drop, designers can:

A. Use smaller wire
B. Up size conductor or shorten runs or add supplies ✓
C. Remove the "EOL"
D. Lower battery size

Up size conductor or shorten runs or add supplies

Definition: Larger gauge conductors and distributed power reduce resistance and drop.

Approved Page 0

Battery sizing typically includes:

A. Standby only
B. Alarm only
C. Both standby time and alarm time with connected loads ✓
D. Breaker size

Both standby time and alarm time with connected loads

Definition: Add quiescent loads for standby and active loads for alarm to meet runtime targets.

Approved Page 0

Secondary power for non voice systems is commonly:

A. 8 hours + 1 minute alarm
B. 24 hours + 5 minutes alarm ✓
C. 24 hours + 15 minutes alarm
D. 12 hours only

24 hours + 5 minutes alarm

Definition: Non voice systems provide a day of standby and five minutes of alarm operation.

Approved Page 0

Secondary power for voice systems is commonly:

A. 24 hours + 1 minute
B. 24 hours + 15 minutes ✓
C. 12 hours + 5 minutes
D. 48 hours + 5 minutes

24 hours + 15 minutes

Definition: Voice systems require fifteen minutes of alarm after standby to deliver messages.

Approved Page 0

Speaker amplifier capacity should be planned with:

A. Zero headroom
B. Some headroom beyond calculated tap totals ✓
C. Double the taps always
D. Random taps

Some headroom beyond calculated tap totals

Definition: Headroom prevents clipping and distortion.

Approved Page 0

Addressable "SLC" loops often include isolators to:

A. Increase loop voltage
B. Segment short circuits so the rest of loop remains operational ✓
C. Reduce supervision
D. Add candela

Segment short circuits so the rest of loop remains operational

Definition: Isolators localize faults and improve survivability.

Approved Page 0

Which cable type is plenum rated for fire alarm?

A. FPL
B. FPLR
C. FPLP ✓
D. CL 2

FPLP

Definition: FPLP is listed for use in environmental air plenums per "NEC" 760.

Approved Page 0

Mixing power limited and non power limited conductors requires:

A. No separation
B. Separation or listed barriers per code and equipment listing ✓
C. Tape labels only
D. Twist them together

Separation or listed barriers per code and equipment listing

Definition: Maintain separation to avoid high voltage damaging low voltage insulation.

Approved Page 0

The fire alarm control unit branch circuit should be:

A. Shared with lighting
B. Dedicated and identified, with disconnect lockable in the ON position ✓
C. On any available breaker
D. On "GFCI" by default

Dedicated and identified, with disconnect lockable in the ON position

Definition: Dedicated, identified power reduces accidental shutoff and keeps the system available.

Approved Page 0

Trouble signals should annunciate within approximately:

A. 10 seconds
B. 60 seconds
C. 200 seconds ✓
D. 20 minutes

200 seconds

Definition: Indicating troubles in a timely manner helps maintain system reliability.

Approved Page 0

For Class N pathways, designers should provide:

A. Unmanaged consumer switches
B. Monitored network segments with power diversity ✓
C. No supervision
D. Wi Fi only

Monitored network segments with power diversity

Definition: Class N covers supervised Ethernet transport; monitor links and provide backup power.

Approved Page 0

A distribution power supply used for strobes must be:

A. Any "DC" supply
B. Listed for fire alarm and supervised for fault conditions ✓
C. Unlisted but fused
D. Powered from receptacle only

Listed for fire alarm and supervised for fault conditions

Definition: Use listed, supervised supplies so failures report to the system.

Approved Page 0

Calculated "NAC" end of line voltage must be:

A. Equal to panel voltage
B. Within the appliance’s listed operating range under worst case ✓
C. Half panel voltage
D. Unimportant

Within the appliance’s listed operating range under worst case

Definition: End devices must still receive adequate voltage to meet performance and sync.

Approved Page 0

Battery strings should be replaced:

A. With mixed ages and Ah ratings
B. With matched, listed type and capacity, and recorded install date ✓
C. Only when dead
D. With car batteries

With matched, listed type and capacity, and recorded install date

Definition: Matched, listed batteries ensure proper charging and runtime.

Approved Page 0

A common cause of false voltage drop failures in practice is:

A. Using larger gauge wire
B. Loose terminations and excessive series resistance ✓
C. Short runs
D. New batteries

Loose terminations and excessive series resistance

Definition: High resistance at poor connections increases voltage loss at devices.

Approved Page 0

Documentation for power calculations should include:

A. Just a total Ah number
B. Device counts, taps, wire sizes, run lengths, and math steps ✓
C. A photo of panel
D. Only the panel data sheet

Device counts, taps, wire sizes, run lengths, and math steps

Definition: Clear documentation supports review, acceptance, and future service.

Approved Page 0

A supervising station is a facility that:

A. Stores spare parts
B. Receives and processes signals from protected premises and initiates response ✓
C. Only prints test reports
D. Controls elevators directly

Receives and processes signals from protected premises and initiates response

Definition: The supervising station monitors alarm, supervisory, and trouble signals and dispatches per the service agreement.

Approved Page 0

Which transmission approach improves availability?

A. Single unsupervised path
B. Dual diverse paths or an enhanced supervised single path ✓
C. Store and forward only
D. Unlisted radio

Dual diverse paths or an enhanced supervised single path

Definition: Redundant or enhanced supervised paths reduce the chance that a single failure blocks reporting.

← Previous Page 13 of 24 Next →