Edit Approved Items

Edit your approved study bank (583 total items)

Showing 301-325 of 583 items

Approved Page 0

Wireless fire detection systems must:

A. Use any consumer wifi
B. Be listed for the application and maintain supervision and power requirements βœ“
C. Use unlisted batteries
D. Avoid supervision

Be listed for the application and maintain supervision and power requirements

Definition: Wireless components must be listed and maintain supervision, tamper, and power performance.

Approved Page 0

Multi criteria detectors combine sensors to:

A. Increase nuisance alarms
B. Improve detection reliability and reduce non fire alarms βœ“
C. Replace manual stations
D. Eliminate maintenance

Improve detection reliability and reduce non fire alarms

Definition: Using multiple sensing technologies can better discriminate fire from non fire phenomena.

Approved Page 0

For elevator lobbies, detector placement should consider:

A. Distance from doors and air movement βœ“
B. Only ceiling color
C. Only floor covering
D. Only light fixtures

Distance from doors and air movement

Definition: Door piston winds and air currents can move smoke; avoid dead air and drafts to ensure timely detection.

Approved Page 0

Class A initiating loops are preferred over Class B when:

A. Shortest wiring is required
B. Increased survivability past a single open is desired βœ“
C. No supervision is needed
D. Voltage is unknown

Increased survivability past a single open is desired

Definition: Class A loops maintain operation beyond a single open by providing a return path.

Approved Page 0

Class B circuits require what at the end of line?

A. Nothing
B. A capacitor
C. An "EOL" resistor at the last device βœ“
D. A diode

An "EOL" resistor at the last device

Definition: The end of line resistor supervises the entire run for opens and grounds.

Approved Page 0

Ground faults should:

A. Be ignored during alarms
B. Annunciate and be located for repair βœ“
C. Be masked to prevent nuisance
D. Only be logged in history

Annunciate and be located for repair

Definition: Grounds can hide other faults; prompt indication and repair are required.

Approved Page 0

"NAC" voltage drop increases primarily with:

A. Shorter wire lengths
B. Lower current
C. Higher current and longer runs βœ“
D. Better splices

Higher current and longer runs

Definition: Voltage drop equals current times resistance; more load and distance increase drop.

Approved Page 0

To reduce "NAC" voltage drop, designers can:

A. Use smaller wire
B. Up size conductor or shorten runs or add supplies βœ“
C. Remove the "EOL"
D. Lower battery size

Up size conductor or shorten runs or add supplies

Definition: Larger gauge conductors and distributed power reduce resistance and drop.

Approved Page 0

Battery sizing typically includes:

A. Standby only
B. Alarm only
C. Both standby time and alarm time with connected loads βœ“
D. Breaker size

Both standby time and alarm time with connected loads

Definition: Add quiescent loads for standby and active loads for alarm to meet runtime targets.

Approved Page 0

Secondary power for non voice systems is commonly:

A. 8 hours + 1 minute alarm
B. 24 hours + 5 minutes alarm βœ“
C. 24 hours + 15 minutes alarm
D. 12 hours only

24 hours + 5 minutes alarm

Definition: Non voice systems provide a day of standby and five minutes of alarm operation.

Approved Page 0

Secondary power for voice systems is commonly:

A. 24 hours + 1 minute
B. 24 hours + 15 minutes βœ“
C. 12 hours + 5 minutes
D. 48 hours + 5 minutes

24 hours + 15 minutes

Definition: Voice systems require fifteen minutes of alarm after standby to deliver messages.

Approved Page 0

Speaker amplifier capacity should be planned with:

A. Zero headroom
B. Some headroom beyond calculated tap totals βœ“
C. Double the taps always
D. Random taps

Some headroom beyond calculated tap totals

Definition: Headroom prevents clipping and distortion.

Approved Page 0

Addressable "SLC" loops often include isolators to:

A. Increase loop voltage
B. Segment short circuits so the rest of loop remains operational βœ“
C. Reduce supervision
D. Add candela

Segment short circuits so the rest of loop remains operational

Definition: Isolators localize faults and improve survivability.

Approved Page 0

Which cable type is plenum rated for fire alarm?

A. FPL
B. FPLR
C. FPLP βœ“
D. CL 2

FPLP

Definition: FPLP is listed for use in environmental air plenums per "NEC" 760.

Approved Page 0

Mixing power limited and non power limited conductors requires:

A. No separation
B. Separation or listed barriers per code and equipment listing βœ“
C. Tape labels only
D. Twist them together

Separation or listed barriers per code and equipment listing

Definition: Maintain separation to avoid high voltage damaging low voltage insulation.

Approved Page 0

The fire alarm control unit branch circuit should be:

A. Shared with lighting
B. Dedicated and identified, with disconnect lockable in the ON position βœ“
C. On any available breaker
D. On "GFCI" by default

Dedicated and identified, with disconnect lockable in the ON position

Definition: Dedicated, identified power reduces accidental shutoff and keeps the system available.

Approved Page 0

Trouble signals should annunciate within approximately:

A. 10 seconds
B. 60 seconds
C. 200 seconds βœ“
D. 20 minutes

200 seconds

Definition: Indicating troubles in a timely manner helps maintain system reliability.

Approved Page 0

For Class N pathways, designers should provide:

A. Unmanaged consumer switches
B. Monitored network segments with power diversity βœ“
C. No supervision
D. Wi Fi only

Monitored network segments with power diversity

Definition: Class N covers supervised Ethernet transport; monitor links and provide backup power.

Approved Page 0

A distribution power supply used for strobes must be:

A. Any "DC" supply
B. Listed for fire alarm and supervised for fault conditions βœ“
C. Unlisted but fused
D. Powered from receptacle only

Listed for fire alarm and supervised for fault conditions

Definition: Use listed, supervised supplies so failures report to the system.

Approved Page 0

Calculated "NAC" end of line voltage must be:

A. Equal to panel voltage
B. Within the appliance’s listed operating range under worst case βœ“
C. Half panel voltage
D. Unimportant

Within the appliance’s listed operating range under worst case

Definition: End devices must still receive adequate voltage to meet performance and sync.

Approved Page 0

Battery strings should be replaced:

A. With mixed ages and Ah ratings
B. With matched, listed type and capacity, and recorded install date βœ“
C. Only when dead
D. With car batteries

With matched, listed type and capacity, and recorded install date

Definition: Matched, listed batteries ensure proper charging and runtime.

Approved Page 0

A common cause of false voltage drop failures in practice is:

A. Using larger gauge wire
B. Loose terminations and excessive series resistance βœ“
C. Short runs
D. New batteries

Loose terminations and excessive series resistance

Definition: High resistance at poor connections increases voltage loss at devices.

Approved Page 0

Documentation for power calculations should include:

A. Just a total Ah number
B. Device counts, taps, wire sizes, run lengths, and math steps βœ“
C. A photo of panel
D. Only the panel data sheet

Device counts, taps, wire sizes, run lengths, and math steps

Definition: Clear documentation supports review, acceptance, and future service.

Approved Page 0

A supervising station is a facility that:

A. Stores spare parts
B. Receives and processes signals from protected premises and initiates response βœ“
C. Only prints test reports
D. Controls elevators directly

Receives and processes signals from protected premises and initiates response

Definition: The supervising station monitors alarm, supervisory, and trouble signals and dispatches per the service agreement.

Approved Page 0

Which transmission approach improves availability?

A. Single unsupervised path
B. Dual diverse paths or an enhanced supervised single path βœ“
C. Store and forward only
D. Unlisted radio

Dual diverse paths or an enhanced supervised single path

Definition: Redundant or enhanced supervised paths reduce the chance that a single failure blocks reporting.

← Previous Page 13 of 24 Next β†’