Edit Approved Items

Edit your approved study bank (583 total items)

Showing 551-575 of 583 items

Approved Page 0

Panel won’t reset after an alarmed smoky kitchen suggests:

A. Normal
B. Residual contamination on detectors; clean per manufacturer βœ“
C. Battery failure only
D. Wire color issue

Residual contamination on detectors; clean per manufacturer

Definition: Residue holds sensors latched; clean and ventilate.

Approved Page 0

If "SLC" devices show duplicate addresses:

A. System works better
B. Communication faults occur; addresses must be unique βœ“
C. Higher speed
D. Battery drain only

Communication faults occur; addresses must be unique

Definition: Duplicates conflict; assign unique addresses per plan.

Approved Page 0

Pull station at 60 inches AFF is:

A. Typical
B. Higher than common accessible range; relocate per design practice βœ“
C. Perfect
D. Required everywhere

Higher than common accessible range; relocate per design practice

Definition: Accessible reach typically targets the 42 to 48 inch operable height range.

Approved Page 0

Spot smoke detectors on peaked ceilings should be:

A. At the ridge only always
B. Placed per listing and slope rules; often near the peak but avoiding dead air βœ“
C. On the floor
D. Only on walls

Placed per listing and slope rules; often near the peak but avoiding dead air

Definition: Follow slope guidance and avoid stagnant air pockets.

Approved Page 0

Beams deeper than standard allowances require:

A. Ignoring them
B. Closer spacing or placement rules to avoid dead air βœ“
C. Fewer detectors
D. Only heat detectors

Closer spacing or placement rules to avoid dead air

Definition: Deep beams can stratify smoke; adjust spacing/placement.

Approved Page 0

Detectors should be kept how far from supply diffusers (typical practice)?

A. No limit
B. A few feet to avoid drafts βœ“
C. At the diffuser
D. Inside the duct

A few feet to avoid drafts

Definition: Avoid strong air streams that dilute smoke.

Approved Page 0

A trouble that reads '"NAC" Open' means:

A. Normal
B. An open in notification wiring; investigate field run and "EOL" βœ“
C. Only a device alarm
D. Battery weak

An open in notification wiring; investigate field run and "EOL"

Definition: Open circuits break supervision; locate and repair.

Approved Page 0

A tamper switch not reporting valve movement likely indicates:

A. Correct operation
B. Mechanical failure or wiring problem at the switch βœ“
C. Normal
D. Pull station issue

Mechanical failure or wiring problem at the switch

Definition: Tamper should change state when the valve handle moves.

Approved Page 0

A door contact wired NC but programmed NO causes:

A. Correct supervisory
B. Misinterpreted status or constant alarms βœ“
C. Better security
D. No change

Misinterpreted status or constant alarms

Definition: Wiring and programming types must match.

Approved Page 0

If two relays control fan shutdown and one is not supervised:

A. It is okay
B. A single failure can defeat shutdown; use listed supervised control circuits βœ“
C. Better performance
D. Less current

A single failure can defeat shutdown; use listed supervised control circuits

Definition: Life safety control must be supervised and listed.

Approved Page 0

A detector behind a decorative beam often:

A. Sees smoke first
B. Sits in a dead air pocket and delays response βœ“
C. Improves sensitivity
D. Is fine always

Sits in a dead air pocket and delays response

Definition: Avoid obstructions and dead air zones.

Approved Page 0

Programming a duct detector as 'supervisory only' when also initiating egress alarm will:

A. Be correct
B. Conflict with required alarm functions; configure per sequence βœ“
C. Improve audibility
D. Silence horns

Conflict with required alarm functions; configure per sequence

Definition: If used for egress actions, annunciation must match the intended function.

Approved Page 0

An annunciator with no power loss reporting likely lacks:

A. Style
B. Supervised power feed or monitoring of loss βœ“
C. Buttons
D. A door

Supervised power feed or monitoring of loss

Definition: Annunciators should indicate loss of power or communications.

Approved Page 0

Which code family decides WHEN systems are required in new work?

A. "NFPA" 72
B. "NEC"
C. "IBC" adopted by the jurisdiction βœ“
D. Manufacturer data sheet

"IBC" adopted by the jurisdiction

Definition: The building code triggers the need; "NFPA" 72 governs design and installation once required.

Approved Page 0

"NFPA" 101 aligns occupant notification with:

A. Egress strategies and occupancy needs βœ“
B. Only sprinkler type
C. Paint color
D. Door hardware finish

Egress strategies and occupancy needs

Definition: Life Safety Code coordinates notification with means of egress and occupancy.

Approved Page 0

A Class A initiating circuit differs from Class B by:

A. Using fewer wires
B. Providing a return path so a single open does not isolate devices βœ“
C. Being unsupervised
D. Using wireless only

Providing a return path so a single open does not isolate devices

Definition: Class A maintains operation past a single open.

Approved Page 0

Class N pathways apply to:

A. Ethernet based supervised transport for fire alarm traffic βœ“
B. Battery wiring only
C. Thermostats
D. Local bells

Ethernet based supervised transport for fire alarm traffic

Definition: Class N covers supervised network segments.

Approved Page 0

Public mode audibility target is commonly:

A. 5 "dBA" above ambient
B. 10 "dBA" above ambient
C. 15 "dBA" above ambient βœ“
D. 30 "dBA" above ambient

15 "dBA" above ambient

Definition: Fifteen "dBA" above average ambient helps signals stand out.

Approved Page 0

In sleeping rooms, preferred fire tone is:

A. 3 "kHz"
B. 520 hertz, Temporal 3 βœ“
C. Any tone
D. Siren only

520 hertz, Temporal 3

Definition: Low frequency 520 hertz improves arousal from sleep.

Approved Page 0

Strobes visible together must:

A. Flash randomly
B. Be synchronized via listed means βœ“
C. Use different candela
D. Be turned off

Be synchronized via listed means

Definition: Synchronization avoids disorientation.

Approved Page 0

A duct detector used only for equipment shutdown should report:

A. General alarm
B. Supervisory βœ“
C. Trouble only
D. Nothing

Supervisory

Definition: Equipment control without egress impact annunciates supervisory.

Approved Page 0

Two detector cross zone releasing uses:

A. One event only
B. Two independent initiations to discharge agent βœ“
C. Waterflow only
D. Door contacts

Two independent initiations to discharge agent

Definition: Two events reduce inadvertent release.

Approved Page 0

Speaker systems should be designed for:

A. Exact rated watts, no margin
B. Some headroom and intelligibility targets βœ“
C. Random taps
D. Only SPL

Some headroom and intelligibility targets

Definition: Headroom preserves clarity and reduces clipping.

Approved Page 0

Battery sizing sums:

A. Standby only
B. Alarm only
C. Standby plus alarm loads over their required durations βœ“
D. Breaker size only

Standby plus alarm loads over their required durations

Definition: Include both quiescent and active loads with margins.

Approved Page 0

Ground faults should:

A. Be ignored
B. Be annunciated and located for repair βœ“
C. Be silenced
D. Be bypassed

Be annunciated and located for repair

Definition: Grounds can mask other faults and must be repaired.

← Previous Page 23 of 24 Next β†’