Edit your approved study bank (583 total items)
Select the correct answer by clicking the radio button
Showing 251-275 of 583 items
Testing frequency for waterflow and valve supervisory switches is commonly:
Quarterly
Definition: Quarterly testing is typical for these interfaces. Reference: "NFPA" 72 (2022) Chapter 14 "ITM".
When strobes are visible together within the same field of view they must:
Be synchronized with a listed method
Definition: Synchronization avoids disorienting effects and meets code intent. Reference: "NFPA" 72 (2022) Chapter 18.
In spaces with raised floors for data cabling, smoke detection should be:
Both in ceiling and underfloor plenum as needed
Definition: Fires can start under floors; detection in both spaces may be required per application. Reference: "NFPA" 72 (2022) Initiating device applications.
Which best practice supports intelligibility of voice messages?
Provide headroom and verify "STI"/"CIS"
Definition: Maintain amplifier headroom and verify intelligibility metrics in "ADS". Reference: "NFPA" 72 (2022) Chapter 24.
Elevator shunt trip, where used by design, is typically activated by:
Specific heat detection at the equipment/hoistway per approved sequence
Definition: Shunt trip logic relies on specific heat detection points; follow the engineered/approved sequence. Reference: "NFPA" 72 (2022) Elevator functions; "IBC" coordination.
Fire alarm control unit branch circuit should be labeled:
βFire Alarm - Do Not Switchβ and lockable on
Definition: Dedicated, identified, lockable branch minimizes accidental shutoff. Reference: "NFPA" 72 (2022) Power supply connections.
During annual testing, notification appliances should be operated for at least:
5 minutes
Definition: Operating for five minutes helps confirm capacity and performance. Reference: "NFPA" 72 (2022) "ITM".
Pull station protective covers with sounders are:
Permitted when approved by the fire official and compatible with required operation
Definition: Covers may be used to reduce nuisance alarms with "AHJ" approval. Reference: "NFPA" 72 (2022) Manual boxes; model code guidance.
Speaker/strobe in the same view powered by different supplies must:
Share a synchronization method across supplies
Definition: Synchronize visible signals across supplies; coordinate audio zones for clarity. Reference: "NFPA" 72 (2022) Chapter 18.
What should operators do before pressing βAlarm Silenceβ?
Acknowledge and investigate first, then silence if permitted
Definition: Maintain response while controlling sound; alarm remains latched until reset. Reference: "NFPA" 72 (2022) Fundamentals/Operations.
Which devices typically require semi annual function tests?
Duct smoke detectors
Definition: Duct detectors are often tested semi annually including sampling tubes and airflow. Reference: "NFPA" 72 (2022) "ITM" tables.
Which documentation is essential for future modifications?
Sequence matrix, device list, voltage drop and battery calcs, and software revision history
Definition: Comprehensive documentation supports maintenance and expansions. Reference: "NFPA" 72 (2022) Chapter 7.
What common mistake reduces smoke detector effectiveness near ceilings?
Mounting too close to edge/beam or in dead air zones
Definition: Avoid dead air spaces; follow listing tables and obstructions rules. Reference: "NFPA" 72 (2022) Initiating Devices. Texas Fire Alarm Technician - 400Q Master (Part 2: Questions 81-160) Aligned to: "NFPA" 72 (2022), "NEC" 70 (2020) Article 760, "IBC" (2021) Section 907, and "NFPA" 101 (2021). Audio friendly flow: Question, Options A-D, βPauseβ, Answer, then a tuned Definition. Pro tip: Map the word βPauseβ to a 4-6 second delay. Set voice rate to about 1.05-1.15Γ.
Public mode audible notification must be at least how much above the average ambient sound level?
15 "dBA"
Definition: Provide about fifteen "dBA" above average ambient to ensure audibility in public mode. This helps the message cut through normal noise.
In sleeping rooms, which signal is preferred for fire to wake sleeping adults?
Temporal 3 at low frequency 520 hertz
Definition: Low frequency 520 hertz with Temporal 3 cadence is shown by research to awaken sleepers more effectively.
Visible appliances in the same field of view must:
Be synchronized by a listed method
Definition: Synchronization prevents disorientation and meets code intent when multiple strobes are visible together.
Minimum audible level at the pillow in sleeping rooms (unless a listed low frequency appliance is used) is:
75 "dBA"
Definition: Seventy five "dBA" at the pillow is a common target for sleeping areas when low frequency requirements are not specifically met.
For mass notification with non emergency messages, fire alarm events should:
Take priority and pre empt non emergency messages
Definition: Fire alarm has the highest life safety priority; non similar signals must not mask emergency cues.
Intelligibility is verified in which spaces?
Acoustically Distinguishable Spaces as required
Definition: Intelligibility measurements like "STI" or "CIS" apply to "ADS" where voice messages must be understood.
Good intelligibility design keeps amplifier loading:
With headroom below the maximum
Definition: Leaving headroom prevents clipping and preserves clarity for voice messages.
Which is most important for intelligibility?
Appropriate speaker layout and direct to reverberant balance
Definition: Proper speaker placement and acoustic control improve word understanding more than raw loudness.
Private mode audible levels are typically:
Lower than public mode
Definition: Private mode alerts staff and responders; required levels can be less than public mode, depending on application.
In arenas with high ambient levels over about 105 "dBA", designers should rely on:
Visible notification and voice strategies
Definition: At extreme ambient levels, strobes and planned voice systems are needed since audibility alone is ineffective.
Temporal 4 is associated with which hazard?
Carbon monoxide
Definition: Carbon monoxide uses a distinct Temporal 4 pattern to differentiate instructions from fire.
Failing to synchronize strobes in a large room can cause:
Potential confusion or disorientation
Definition: Unsynchronized flashes can appear chaotic, reducing effectiveness and occupant confidence.