Edit Approved Items

Edit your approved study bank (583 total items)

Showing 251-275 of 583 items

Approved Page 0

Testing frequency for waterflow and valve supervisory switches is commonly:

A. Monthly
B. Quarterly βœ“
C. Semi annual
D. Annual

Quarterly

Definition: Quarterly testing is typical for these interfaces. Reference: "NFPA" 72 (2022) Chapter 14 "ITM".

Approved Page 0

When strobes are visible together within the same field of view they must:

A. Have differing flash rates
B. Be synchronized with a listed method βœ“
C. Be random
D. Be turned off

Be synchronized with a listed method

Definition: Synchronization avoids disorienting effects and meets code intent. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

In spaces with raised floors for data cabling, smoke detection should be:

A. Ceiling only
B. Underfloor only
C. Both in ceiling and underfloor plenum as needed βœ“
D. Prohibited due to airflow

Both in ceiling and underfloor plenum as needed

Definition: Fires can start under floors; detection in both spaces may be required per application. Reference: "NFPA" 72 (2022) Initiating device applications.

Approved Page 0

Which best practice supports intelligibility of voice messages?

A. Load amplifiers to 100 percent rated watts
B. Provide headroom and verify "STI"/"CIS" βœ“
C. Use random speaker taps
D. Mount speakers arbitrarily

Provide headroom and verify "STI"/"CIS"

Definition: Maintain amplifier headroom and verify intelligibility metrics in "ADS". Reference: "NFPA" 72 (2022) Chapter 24.

Approved Page 0

Elevator shunt trip, where used by design, is typically activated by:

A. Any detector in building
B. Specific heat detection at the equipment/hoistway per approved sequence βœ“
C. Waterflow
D. Manual pull only

Specific heat detection at the equipment/hoistway per approved sequence

Definition: Shunt trip logic relies on specific heat detection points; follow the engineered/approved sequence. Reference: "NFPA" 72 (2022) Elevator functions; "IBC" coordination.

Approved Page 0

Fire alarm control unit branch circuit should be labeled:

A. Optional
B. β€œFire Alarm - Do Not Switch” and lockable on βœ“
C. With panel serial number only
D. No label by code

β€œFire Alarm - Do Not Switch” and lockable on

Definition: Dedicated, identified, lockable branch minimizes accidental shutoff. Reference: "NFPA" 72 (2022) Power supply connections.

Approved Page 0

During annual testing, notification appliances should be operated for at least:

A. 30 seconds
B. 1 minute
C. 5 minutes βœ“
D. No minimum

5 minutes

Definition: Operating for five minutes helps confirm capacity and performance. Reference: "NFPA" 72 (2022) "ITM".

Approved Page 0

Pull station protective covers with sounders are:

A. Always prohibited
B. Permitted when approved by the fire official and compatible with required operation βœ“
C. Required everywhere
D. A substitute for pull stations

Permitted when approved by the fire official and compatible with required operation

Definition: Covers may be used to reduce nuisance alarms with "AHJ" approval. Reference: "NFPA" 72 (2022) Manual boxes; model code guidance.

Approved Page 0

Speaker/strobe in the same view powered by different supplies must:

A. Operate independently with no sync
B. Share a synchronization method across supplies βœ“
C. Flash at different rates
D. Use amber lenses

Share a synchronization method across supplies

Definition: Synchronize visible signals across supplies; coordinate audio zones for clarity. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

What should operators do before pressing β€œAlarm Silence”?

A. Reset immediately
B. Acknowledge and investigate first, then silence if permitted βœ“
C. Ignore the alarm
D. Disable the panel

Acknowledge and investigate first, then silence if permitted

Definition: Maintain response while controlling sound; alarm remains latched until reset. Reference: "NFPA" 72 (2022) Fundamentals/Operations.

Approved Page 0

Which devices typically require semi annual function tests?

A. Duct smoke detectors βœ“
B. Manual pull stations
C. Heat detectors
D. Door holders

Duct smoke detectors

Definition: Duct detectors are often tested semi annually including sampling tubes and airflow. Reference: "NFPA" 72 (2022) "ITM" tables.

Approved Page 0

Which documentation is essential for future modifications?

A. Only the Record of Completion
B. Sequence matrix, device list, voltage drop and battery calcs, and software revision history βœ“
C. Invoices only
D. Owner’s manual only

Sequence matrix, device list, voltage drop and battery calcs, and software revision history

Definition: Comprehensive documentation supports maintenance and expansions. Reference: "NFPA" 72 (2022) Chapter 7.

Approved Page 0

What common mistake reduces smoke detector effectiveness near ceilings?

A. Mounting too close to edge/beam or in dead air zones βœ“
B. Using listed bases
C. Following ceiling plans
D. Documenting placement

Mounting too close to edge/beam or in dead air zones

Definition: Avoid dead air spaces; follow listing tables and obstructions rules. Reference: "NFPA" 72 (2022) Initiating Devices. Texas Fire Alarm Technician - 400Q Master (Part 2: Questions 81-160) Aligned to: "NFPA" 72 (2022), "NEC" 70 (2020) Article 760, "IBC" (2021) Section 907, and "NFPA" 101 (2021). Audio friendly flow: Question, Options A-D, β€œPause”, Answer, then a tuned Definition. Pro tip: Map the word β€œPause” to a 4-6 second delay. Set voice rate to about 1.05-1.15Γ—.

Approved Page 0

Public mode audible notification must be at least how much above the average ambient sound level?

A. 5 "dBA"
B. 10 "dBA"
C. 15 "dBA" βœ“
D. 20 "dBA"

15 "dBA"

Definition: Provide about fifteen "dBA" above average ambient to ensure audibility in public mode. This helps the message cut through normal noise.

Approved Page 0

In sleeping rooms, which signal is preferred for fire to wake sleeping adults?

A. Temporal 3 at 1 kilohertz
B. Temporal 3 at low frequency 520 hertz βœ“
C. Temporal 4 at 520 hertz
D. Continuous 3 kilohertz

Temporal 3 at low frequency 520 hertz

Definition: Low frequency 520 hertz with Temporal 3 cadence is shown by research to awaken sleepers more effectively.

Approved Page 0

Visible appliances in the same field of view must:

A. Flash randomly
B. Be synchronized by a listed method βœ“
C. Use different candela values
D. Be on the same power supply

Be synchronized by a listed method

Definition: Synchronization prevents disorientation and meets code intent when multiple strobes are visible together.

Approved Page 0

Minimum audible level at the pillow in sleeping rooms (unless a listed low frequency appliance is used) is:

A. 65 "dBA"
B. 70 "dBA"
C. 75 "dBA" βœ“
D. 85 "dBA"

75 "dBA"

Definition: Seventy five "dBA" at the pillow is a common target for sleeping areas when low frequency requirements are not specifically met.

Approved Page 0

For mass notification with non emergency messages, fire alarm events should:

A. Yield to MNS messages
B. Share equal priority
C. Take priority and pre empt non emergency messages βœ“
D. Be disabled during messages

Take priority and pre empt non emergency messages

Definition: Fire alarm has the highest life safety priority; non similar signals must not mask emergency cues.

Approved Page 0

Intelligibility is verified in which spaces?

A. All rooms regardless
B. Only corridors
C. Acoustically Distinguishable Spaces as required βœ“
D. Mechanical rooms only

Acoustically Distinguishable Spaces as required

Definition: Intelligibility measurements like "STI" or "CIS" apply to "ADS" where voice messages must be understood.

Approved Page 0

Good intelligibility design keeps amplifier loading:

A. At 100 percent of rated watts
B. With headroom below the maximum βœ“
C. Overdriven for loudness
D. Irrelevant

With headroom below the maximum

Definition: Leaving headroom prevents clipping and preserves clarity for voice messages.

Approved Page 0

Which is most important for intelligibility?

A. Highest possible sound level
B. Appropriate speaker layout and direct to reverberant balance βœ“
C. More strobes
D. Lower voltage

Appropriate speaker layout and direct to reverberant balance

Definition: Proper speaker placement and acoustic control improve word understanding more than raw loudness.

Approved Page 0

Private mode audible levels are typically:

A. Lower than public mode βœ“
B. Higher than public mode
C. Equal to public mode
D. Not defined

Lower than public mode

Definition: Private mode alerts staff and responders; required levels can be less than public mode, depending on application.

Approved Page 0

In arenas with high ambient levels over about 105 "dBA", designers should rely on:

A. Audible only
B. Visible notification and voice strategies βœ“
C. No notification
D. Just a local bell

Visible notification and voice strategies

Definition: At extreme ambient levels, strobes and planned voice systems are needed since audibility alone is ineffective.

Approved Page 0

Temporal 4 is associated with which hazard?

A. Fire
B. Carbon monoxide βœ“
C. Security breach
D. Sprinkler waterflow

Carbon monoxide

Definition: Carbon monoxide uses a distinct Temporal 4 pattern to differentiate instructions from fire.

Approved Page 0

Failing to synchronize strobes in a large room can cause:

A. Improved visibility
B. No impact
C. Potential confusion or disorientation βœ“
D. Lower current draw

Potential confusion or disorientation

Definition: Unsynchronized flashes can appear chaotic, reducing effectiveness and occupant confidence.

← Previous Page 11 of 24 Next β†’