Edit Approved Items

Edit your approved study bank (583 total items)

Showing 226-250 of 583 items

Approved Page 0

Mixing power limited and non power limited conductors requires:

A. No separation
B. Separation or barriers per code and equipment listing βœ“
C. Only twisted pairs
D. Using thermostat cable

Separation or barriers per code and equipment listing

Definition: Maintain separation or listed barriers to prevent higher voltages compromising low voltage insulation. Reference: "NEC" 70 (2020) Article 760; "NFPA" 72 (2022).

Approved Page 0

Power for the fire alarm control unit should be on a branch that is:

A. Shared with lighting
B. Dedicated, identified, and lockable in the ON position βœ“
C. On a local toggle
D. On "GFCI"/"AFCI" by default

Dedicated, identified, and lockable in the ON position

Definition: A dedicated, identified branch reduces accidental shutoff. Reference: "NFPA" 72 (2022) Fundamentals; coordination with "NEC".

Approved Page 0

Notification Appliance Circuit voltage drop verification should confirm:

A. Panel terminal voltage only
B. First device voltage only
C. Worst case device meets minimum voltage at the end of line βœ“
D. No verification needed

Worst case device meets minimum voltage at the end of line

Definition: Check the end of line under worst case to avoid dim/unsynced appliances. Reference: "NFPA" 72 (2022) Design Practices.

Approved Page 0

A single robust off premises path (e.g., cellular) should:

A. Need no supervision
B. Detect/report a failure within a short window (often minutes) βœ“
C. Be tested yearly only
D. Use dial up only

Detect/report a failure within a short window (often minutes)

Definition: Enhanced single paths require rapid fault detection; dual paths provide diversity. Reference: "NFPA" 72 (2022) Chapter 26.

Approved Page 0

Ground faults on fire alarm wiring must be:

A. Ignored if no alarm
B. Indicated promptly and located for repair βœ“
C. Cleared automatically
D. Only logged

Indicated promptly and located for repair

Definition: Indicate grounds so they can be repaired; grounds can mask other faults. Reference: "NFPA" 72 (2022) Circuits and Pathways.

Approved Page 0

Class A versus Class B initiating circuits differ because Class A:

A. Uses fewer wires
B. Has a return path so one open does not isolate devices βœ“
C. Is wireless
D. Is not supervised

Has a return path so one open does not isolate devices

Definition: Class A has an alternate path; Class B does not. Reference: "NFPA" 72 (2022) Pathways.

Approved Page 0

Class N applies to:

A. Speaker circuits
B. Network "IP" pathways for fire alarm traffic with supervision βœ“
C. Non power limited circuits
D. Thermostat loops

Network "IP" pathways for fire alarm traffic with supervision

Definition: Class N covers supervised Ethernet based transport. Reference: "NFPA" 72 (2022) Pathways.

Approved Page 0

Color coding of fire alarm conductors is:

A. Strictly mandated red by code
B. Not mandated by color but identification at terminations is required by practice/code βœ“
C. Mandated blue
D. Mandated yellow

Not mandated by color but identification at terminations is required by practice/code

Definition: Identify fire alarm circuits; red is customary but the key is clear identification at terminations and junctions. Reference: "NEC" 70 (2020) Article 760 identification.

Approved Page 0

Which device state should report supervisory rather than general alarm?

A. Closed sprinkler control valve (tamper) βœ“
B. Manual pull station
C. Smoke detector in an area
D. Heat detector activation

Closed sprinkler control valve (tamper)

Definition: Off normal conditions like closed valves are supervisory, prompting correction before an event. Reference: "NFPA" 72 (2022) Supervisory Signals.

Approved Page 0

What is alarm verification feature (AVF) used for on some smoke detectors/systems?

A. Speed evacuation
B. Reduce nuisance by re checking a signal before latching alarm βœ“
C. Disable detectors
D. Replace duct detection

Reduce nuisance by re checking a signal before latching alarm

Definition: AVF temporarily delays to confirm smoke conditions and reduce nuisance alarms (not for heat/manual). Reference: "NFPA" 72 (2022) Initiating Devices.

Approved Page 0

During an impairment that disables protection, the responsible party should:

A. Ignore it
B. Implement a fire watch per policy and notify stakeholders βœ“
C. Silence the panel only
D. Remove pull stations

Implement a fire watch per policy and notify stakeholders

Definition: Use documented fire watch and notifications during impairments. Reference: "NFPA" 72 (2022) "ITM"/Impairments.

Approved Page 0

Battery replacement should be:

A. Any 12 V battery will do
B. Per listing/type and capacity; mark install date βœ“
C. Only when it fails
D. Mix old and new batteries

Per listing/type and capacity; mark install date

Definition: Use listed batteries of correct amp hour and date mark for maintenance. Reference: "NFPA" 72 (2022) Power Supplies/"ITM".

Approved Page 0

At acceptance, how much of the system must be tested?

A. 10 percent sample
B. 25 percent sample
C. 50 percent sample
D. 100 percent of devices and functions βœ“

100 percent of devices and functions

Definition: Acceptance is 100 percent device and function testing. Reference: "NFPA" 72 (2022) Chapter 14.

Approved Page 0

Speaker circuits for voice/alarm communication systems are typically:

A. Class B only
B. Required Class A or with survivability measures per design βœ“
C. Not supervised
D. "DC" horns

Required Class A or with survivability measures per design

Definition: Provide survivability via Class A or other measures to keep messaging during faults. Reference: "NFPA" 72 (2022) Chapter 24 ("EVACS").

Approved Page 0

Mass notification or non emergency strobes operating with fire strobes should:

A. Continue and be unsynchronized
B. Be controlled so fire alarm cues take precedence βœ“
C. Override fire strobes
D. Flash randomly

Be controlled so fire alarm cues take precedence

Definition: Fire alarm signals have priority; non similar signals should not mask them. Reference: "NFPA" 72 (2022) Chapter 18 priorities.

Approved Page 0

A trouble indication must annunciate at the panel within approximately:

A. 10 seconds
B. 60 seconds
C. 200 seconds βœ“
D. 5 minutes

200 seconds

Definition: Code limits exist for indicating troubles; about 200 seconds is typical for certain faults. Reference: "NFPA" 72 (2022) Fundamentals.

Approved Page 0

What is the best practice location for remote annunciators?

A. Hidden office
B. Near main entrances or fire command locations βœ“
C. Mechanical penthouse only
D. Basement only

Near main entrances or fire command locations

Definition: Place where first responders arrive to speed size up. Reference: "NFPA" 72 (2022) Annunciation practice.

Approved Page 0

What should be documented for "NAC" calculations?

A. Only final amp hours
B. Full device counts, wire sizes, lengths, and math for voltage drop and battery sizing βœ“
C. Nothing if it works
D. A photo of the panel only

Full device counts, wire sizes, lengths, and math for voltage drop and battery sizing

Definition: Provide full calculations and assumptions in submittals and acceptance docs. Reference: "NFPA" 72 (2022) Documentation.

Approved Page 0

Which code determines when a new occupancy must have a fire alarm system?

A. "NFPA" 72
B. "NFPA" 101 only
C. "IBC" (Section 907) βœ“
D. "NEC" Article 760

"IBC" (Section 907)

Definition: The building code triggers the requirement; "NFPA" 72 governs design/installation of the system once required. Reference: "IBC" (2021) Β§907.

Approved Page 0

Areas with very high ambient noise (over about 105 "dBA") require:

A. More horns only
B. Rely on visual notification (strobes) and other means; audibility may be ineffective βœ“
C. No notification
D. Lowering ambient noise

Rely on visual notification (strobes) and other means; audibility may be ineffective

Definition: Above extreme ambient levels, visible notification is primary and voice may be needed. Reference: "NFPA" 72 (2022) Notification.

Approved Page 0

Voice/alarm communication systems must be intelligible in:

A. All spaces regardless
B. Acoustically distinguishable spaces ("ADS") as required βœ“
C. Mechanical rooms only
D. Corridors only

Acoustically distinguishable spaces ("ADS") as required

Definition: Provide intelligibility where required; measure "STI" or "CIS" as applicable. Reference: "NFPA" 72 (2022) Chapter 24.

Approved Page 0

Where an occupancy relies on manual boxes, what is a common exception to placing a box at every exit?

A. If fully sprinklered and the fire alarm is automatically activated, some locations may be omitted by code βœ“
B. If the owner prefers
C. If there is a guard desk
D. If there are "CCTV" cameras

If fully sprinklered and the fire alarm is automatically activated, some locations may be omitted by code

Definition: Model codes permit reduced pull station count in fully sprinklered buildings with automatic detection/activation, subject to "AHJ" approval. Reference: "IBC" (2021) Β§907; "NFPA" 72 (2022).

Approved Page 0

Carbon monoxide life safety signaling pattern differs from fire by using:

A. Temporal 3
B. Temporal 4 distinct pattern and labeling βœ“
C. Continuous tone
D. Same as fire

Temporal 4 distinct pattern and labeling

Definition: Carbon monoxide uses aT 4 pattern distinct from fire’sT 3 for clear occupant action. Reference: "NFPA" 72 (2022) Notification; combination systems.

Approved Page 0

For dormitories/apartments (Group R), low frequency 520 hertz appliances are required in sleeping rooms primarily due to:

A. Aesthetic reasons
B. Improved awakening effectiveness for sleeping adults βœ“
C. Easier wiring
D. Lower current draw

Improved awakening effectiveness for sleeping adults

Definition: Research shows 520 hertz signals wake sleepers more effectively. Reference: "NFPA" 72 (2022) Notification; "IBC"/ "NFPA" 101 occupancies.

Approved Page 0

Which of the following typically requires monitoring by the fire alarm system?

A. Closed sprinkler control valve position βœ“
B. Ceiling fan status
C. Elevator door chimes
D. Lighting dimmers

Closed sprinkler control valve position

Definition: Supervise sprinkler valves to catch impairments; signal is supervisory. Reference: "NFPA" 72 (2022) Supervisory signals; "NFPA" 13/ "IBC" integration.

← Previous Page 10 of 24 Next β†’