Edit your approved study bank (583 total items)
Select the correct answer by clicking the radio button
Showing 351-375 of 583 items
If an "EOL" is mistakenly placed in the panel on a Class B initiating circuit, supervision of what portion is lost?
The field wiring beyond the panel
Definition: "EOL" must be at the last device to supervise the entire path for opens/grounds.
A single open on a Class A "SLC" will:
Still allow communication past the break via the return path
Definition: Class A provides an alternate path; a single open should not isolate downstream devices.
A 24 "VDC" "NAC" at 3.0 amps on long 18 "AWG" runs likely risks:
Low candela at the end devices
Definition: High current and small gauge increase drop; end devices can dim or mis sync.
Using distributed power supplies near remote loads primarily:
Reduces run length and voltage drop
Definition: Closer supplies shorten conductor length and help maintain device voltage.
For a two detector cross zone release, activation requires:
Two independent initiating events
Definition: Two independent inputs help prevent inadvertent discharge.
A corridor 8 feet wide typically uses spacing for spot smoke detectors of about:
41 feet
Definition: Corridor rules allow approximately forty one feet on center for narrow corridors.
Beam smoke detection is most efficient when ceilings are:
Very high with long spans
Definition: Beams cover long distances and are suited to high or wide open spaces.
If ambient temperature can reach 120 F, an ordinary 135 F fixed temperature heat detector:
Should be avoided; choose a higher rating
Definition: Select heat detector ratings at least 25 F above the highest expected ambient.
For a speaker zone requiring intelligibility, the best first step is to:
Optimize speaker spacing and aim
Definition: Layout and aiming improve direct to reverberant ratio and clarity.
A device label indicating 16-33 "VDC" operating range means end of line voltage should be:
Within 16 to 33 V under worst case
Definition: Verify that worst case end voltage stays within the listed range for reliable operation.
A 24 V control relay used for fan shutdown should be powered:
From a listed, supervised control circuit
Definition: Life safety control circuits must be listed and supervised for faults.
Class N pathways are used for:
Supervised Ethernet "IP" signaling for fire alarm traffic
Definition: Class N covers supervised network transport segments with monitoring.
An addressable "SLC" map that mirrors the floor plan helps with:
Troubleshooting and response speed
Definition: Clear point text and maps speed fault finding and emergency response.
A ground fault indicated at the panel should be located by:
Logically splitting circuits to isolate segments
Definition: Open loops in halves or segments to locate the fault efficiently.
A short on a Class B initiating circuit will:
Indicate trouble and possibly prevent detection on that run
Definition: Shorts defeat normal supervision; panel will show trouble and the run may be inoperative.
A missing "EOL" resistor on Class B "IDC" will:
Annunciate as trouble
Definition: Missing or wrong "EOL" presents as a trouble condition.
Device addresses on an "SLC" should be:
Unique and matched to drawings and labels
Definition: Unique addresses with clear point text speed service and response.
When a circuit is intermittent, the likely cause is:
Temperature sensitive loose connections or water intrusion
Definition: Loose or wet connections can vary with temperature or vibration.
If strobes on two supplies are unsynchronized in one room, you should:
Add a listed sync connection or compatible supplies
Definition: Use a listed method so flashes align across supplies.
Placing an "EOL" in the panel on a "NAC" will:
Supervise only the panel terminals
Definition: "EOL" in the panel fails to supervise the run; place it at the last appliance unless the supply supervises downstream wiring by other means.
A duct detector downstream of filters fails to trip on smoke can indicate:
Reversed sampling tubes or poor airflow
Definition: Verify tube orientation and pressure; reversed tubes prevent sampling.
Addressable device not communicating after replacement usually means:
Wrong address, missing "SLC" isolator reset, or reversed polarity
Definition: Check address, polarity, and whether an isolator has latched open from a prior short.
Door holders stuck open during alarm suggest:
Unsupervised power supply feeding holders
Definition: Holders should drop on alarm or power loss; unsupervised feeds can defeat this behavior.
If a module LED flashes but no event logs, the input type may be:
Configured as disabled or wrong type
Definition: Programming must match the wiring and function type for proper event generation.
A panel that wonβt reset after a smoky event may require:
Ventilation and detector cleaning per manufacturer
Definition: Residual smoke or contamination holds detectors in alarm; clean per instructions.