Edit Approved Items

Edit your approved study bank (583 total items)

Showing 376-400 of 583 items

Approved Page 0

Frequent false alarms near restrooms usually indicate:

A. Perfect location
B. Steam or aerosol sources too close to smoke detectors ✓
C. Good practice
D. No impact

Steam or aerosol sources too close to smoke detectors

Definition: Keep detectors away from steam sources to reduce nuisance.

Approved Page 0

Elevator recall not occurring on lobby smoke suggests:

A. Correct wiring
B. Detector not mapped to elevator control logic ✓
C. Nothing wrong
D. Pull station fixes it

Detector not mapped to elevator control logic

Definition: Ensure the lobby detector is programmed to drive the recall sequence.

Approved Page 0

A failing battery string often shows as:

A. Stable standby voltage and passing load test
B. Low under load voltage or short alarm runtime ✓
C. Higher capacity than rated
D. Improved charging

Low under load voltage or short alarm runtime

Definition: Load testing reveals weak capacity despite normal open circuit voltage.

Approved Page 0

A reversed "NAC" polarity during alarm typically causes:

A. Normal operation
B. Appliances to remain silent or unsupervised ✓
C. Brighter strobes
D. Higher candela

Appliances to remain silent or unsupervised

Definition: Many appliances and supervision rely on correct polarity.

Approved Page 0

A frozen tamper switch indicates:

A. Normal valve position
B. Mechanical issue or wiring fault in the tamper device ✓
C. No problem
D. Waterflow

Mechanical issue or wiring fault in the tamper device

Definition: Tamper devices should change state with valve movement; stuck state needs repair.

Approved Page 0

A door magnetic contact that bounces causes:

A. Stable input
B. Intermittent alarms/supervisory ✓
C. Nothing
D. Battery damage

Intermittent alarms/supervisory

Definition: Chattering contacts generate intermittent signals; debounce or replace.

Approved Page 0

If an annunciator shows 'Ground Fault - Loop 2', first step is:

A. Replace all devices
B. Open the loop mid run and see if the fault clears ✓
C. Ignore it
D. Short the loop

Open the loop mid run and see if the fault clears

Definition: Splitting the loop isolates which half contains the fault.

Approved Page 0

An "SLC" device reading 'Missing' after construction work suggests:

A. Perfect communication
B. Open in cabling or removed device ✓
C. Normal state
D. Panel failure

Open in cabling or removed device

Definition: Wiring damage or removed devices commonly cause missing points.

Approved Page 0

Which code family decides WHEN a fire alarm is required for a new building?

A. "NFPA" 72
B. "NEC"
C. "IBC" model building code adopted by the jurisdiction ✓
D. Manufacturer manual

"IBC" model building code adopted by the jurisdiction

Definition: Building code adoption determines where a system is required; "NFPA" 72 tells how to design/install it.

Approved Page 0

Group R sleeping occupancies typically require low frequency 520 hertz appliances in sleeping rooms to:

A. Save power
B. Improve awakening effectiveness ✓
C. Reduce cost
D. Ease wiring

Improve awakening effectiveness

Definition: Low frequency tone improves arousal from sleep; coordinate with local adoption.

Approved Page 0

In fully sprinklered buildings with automatic detection, some manual box locations may be omitted when:

A. The owner prefers
B. Permitted by code exceptions and approved by the "AHJ" ✓
C. Never
D. Only in warehouses

Permitted by code exceptions and approved by the "AHJ"

Definition: Model codes allow reductions when automatic systems provide early activation; verify the local rule.

Approved Page 0

Assembly occupancies with high ambient noise need:

A. Horns only
B. Visible notification and voice as needed ✓
C. No notification
D. Security only

Visible notification and voice as needed

Definition: High noise can mask horns; strobes and voice reduce risk.

Approved Page 0

Educational occupancies often require:

A. No detection
B. Manual boxes along egress and detection as required by use ✓
C. Only duct detectors
D. Horns only

Manual boxes along egress and detection as required by use

Definition: Egress notification and detection are coordinated with building code triggers.

Approved Page 0

Health care occupancies (hospitals) often use:

A. Evacuation of all occupants immediately
B. Defend in place with compartmentation and staff response ✓
C. No alarm
D. Only strobes

Defend in place with compartmentation and staff response

Definition: Life Safety Code permits defend in place with staff and compartmentation; voice messaging is common.

Approved Page 0

Hotels (R 1) sleeping rooms typically require:

A. No in room notification
B. Notification appliances in sleeping rooms per code and low frequency where required ✓
C. Only corridor horns
D. Only strobes in lobby

Notification appliances in sleeping rooms per code and low frequency where required

Definition: In room appliances alert sleeping guests; low frequency devices where adopted.

Approved Page 0

High rise buildings require which additional features?

A. Nothing special
B. Fire command center and dedicated functions per building code ✓
C. Security guards only
D. Only duct detectors

Fire command center and dedicated functions per building code

Definition: High rise provisions include command centers, FD communications, and additional controls.

Approved Page 0

Areas of refuge and stairwells may require:

A. No communications
B. Firefighter telephone or two way communications per design ✓
C. Only horns
D. Music paging

Firefighter telephone or two way communications per design

Definition: Provide emergency communications where specified by code.

Approved Page 0

Atrium detection approaches commonly include:

A. Spot only at floor
B. Beam or aspiration with zoning and voice messaging ✓
C. No detection
D. Only duct detectors

Beam or aspiration with zoning and voice messaging

Definition: Large volumes benefit from beam or aspirating detection and integrated voice.

Approved Page 0

Smoke control in large buildings is documented as:

A. A phone call
B. A written sequence/matrix with priorities and fail safe states ✓
C. Only a diagram
D. Left to HV "AC" vendor only

A written sequence/matrix with priorities and fail safe states

Definition: Sequences must be documented for testing and operations.

Approved Page 0

In dwelling units, combination fire and carbon monoxide alarms should:

A. Use the same pattern for both
B. Provide distinct patterns and labeling ✓
C. Use amber light only
D. Be silent

Provide distinct patterns and labeling

Definition: Distinct cues help occupants take correct actions.

Approved Page 0

Where audible notification is impractical due to hearing impaired occupants, you should:

A. Do nothing
B. Provide visible appliances and possibly text/voice paging ✓
C. Only louder horns
D. Rely on security radios

Provide visible appliances and possibly text/voice paging

Definition: Visual and alternative communications address accessibility.

Approved Page 0

For small B (Business) offices with low risk, a common trigger for a full system is:

A. Always required
B. Sprinkler monitoring or specific area detection per code triggers ✓
C. Never required
D. Only security sensors

Sprinkler monitoring or specific area detection per code triggers

Definition: Building code defines thresholds; monitoring and specific risks trigger systems.

Approved Page 0

For hazardous materials rooms, designers should:

A. Avoid detection
B. Coordinate detection, ventilation shutoff, and alarm per risk and code ✓
C. Use music speakers
D. Only door contacts

Coordinate detection, ventilation shutoff, and alarm per risk and code

Definition: Provide detection and controls to limit hazard spread.

Approved Page 0

Dormitory corridors typically require:

A. Only exit signs
B. Notification and detection as required; corridor smoke in some designs ✓
C. Only duct detectors
D. Nothing

Notification and detection as required; corridor smoke in some designs

Definition: Corridor notification and sometimes smoke detection coordinate with egress strategy.

Approved Page 0

Assisted living facilities often need:

A. No system
B. Manual boxes, detection, and occupant notification per residential care requirements ✓
C. Only strobes
D. Only waterflow

Manual boxes, detection, and occupant notification per residential care requirements

Definition: Residential care occupancies require system features suitable for mobility limited residents.

← Previous Page 16 of 24 Next →