Edit Approved Items

Edit your approved study bank (583 total items)

Showing 201-225 of 583 items

Approved Page 0

Which Texas relevant best practice improves response for first arriving crews?

A. Place remote annunciator at a hidden office
B. Place remote annunciator near main entrance or command location ✓
C. Do not install annunciators
D. Install only a local bell

Place remote annunciator near main entrance or command location

Definition: Providing annunciation where responders arrive speeds size up and reduces delay. Reference: "NFPA" 72 (2022) Protected Premises practices.

Approved Page 0

What must be completed before owner acceptance?

A. 10 percent sampling
B. 100 percent device testing with documented results ✓
C. Visual inspection only
D. Battery test only

100 percent device testing with documented results

Definition: Acceptance testing verifies every initiating and notification device and sequence functions. Reference: "NFPA" 72 (2022) Chapter 14.

Approved Page 0

Which events require occupant notification to take precedence over non emergency signals?

A. Security flashing lights
B. Background paging
C. Both of these ✓
D. Neither of these

Both of these

Definition: Fire alarm notification takes priority over non similar signals to avoid masking emergency cues. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

In sleeping rooms, fire audible appliances must produce what signal pattern and frequency?

A. Temporal 3 at 520 hertz low frequency ✓
B. Temporal 4 at 3150 hertz
C. Continuous tone at 1 kilohertz
D. Any pulsed tone

Temporal 3 at 520 hertz low frequency

Definition: Sleeping areas use low frequency 520 hertz appliances for fire with Temporal 3 cadence to improve awakening. Reference: "NFPA" 72 (2022) Notification; research based requirement.

Approved Page 0

Public mode audibility should be at least how much above average ambient?

A. 5 "dBA"
B. 10 "dBA"
C. 15 "dBA" ✓
D. 20 "dBA"

15 "dBA"

Definition: Provide about fifteen "dBA" above average ambient for public mode audibility. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

Minimum level at the pillow in sleeping rooms is typically:

A. 65 "dBA"
B. 70 "dBA"
C. 75 "dBA" ✓
D. 85 "dBA"

75 "dBA"

Definition: Aim for at least seventy five "dBA" at the pillow unless a listed low frequency signal is provided. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

Where should duct smoke detectors be installed on supply systems?

A. Upstream of filters
B. Downstream of filters and ahead of branch connections ✓
C. At every diffuser
D. Only in return ducts

Downstream of filters and ahead of branch connections

Definition: Locate downstream of filters and before branches to detect smoke prior to distribution. Reference: "NFPA" 72 (2022) Duct Detection.

Approved Page 0

If a duct detector is used only to shut down equipment, what signal should it generate at the panel?

A. General alarm
B. Supervisory ✓
C. No signal
D. Trouble

Supervisory

Definition: Equipment control only duct detection annunciates supervisory, not general alarm. Reference: "NFPA" 72 (2022) Application of detectors.

Approved Page 0

Manual pull stations should be installed:

A. On random walls
B. On the path of egress near exit doors, typically within about 5 feet ✓
C. Inside electrical rooms only
D. Only at one location

On the path of egress near exit doors, typically within about 5 feet

Definition: Place pull stations on egress paths near exit doorways for quick access. Reference: "NFPA" 72 (2022); "IBC" (2021) §907.

Approved Page 0

Beam smoke detectors are most appropriate for:

A. Small 8 ft offices
B. High or wide open spaces like atria and warehouses ✓
C. Wet locations only
D. Confined shafts

High or wide open spaces like atria and warehouses

Definition: Beam detectors cover long spans and high ceilings efficiently when point detectors are impractical. Reference: "NFPA" 72 (2022) Initiating Devices.

Approved Page 0

Elevator Phase One recall is typically initiated by:

A. Heat in the cab
B. Smoke detection in lobbies, hoistways, or machine rooms (per design) ✓
C. Pull stations only
D. Sprinkler waterflow only

Smoke detection in lobbies, hoistways, or machine rooms (per design)

Definition: Smoke detection in designated elevator areas triggers recall to a primary landing. Reference: "NFPA" 72 (2022) Elevator interfaces; building code coordination.

Approved Page 0

Kitchen hood fire extinguishing system connection to the fire alarm should:

A. Do nothing
B. Initiate fire alarm and programmed control functions ✓
C. Create supervisory only
D. Only shut makeup air

Initiate fire alarm and programmed control functions

Definition: Discharge is a fire event that activates alarm and required control actions per the sequence. Reference: "NFPA" 72 (2022) Emergency control functions.

Approved Page 0

Smoke detector sensitivity must be checked:

A. Only at installation
B. Within one year after installation and then at intervals per code (often every two years unless extended) ✓
C. Every month
D. Never

Within one year after installation and then at intervals per code (often every two years unless extended)

Definition: Verify sensitivity after installation and periodically thereafter; performance based options may adjust intervals. Reference: "NFPA" 72 (2022) Chapter 14.

Approved Page 0

Short circuit isolators on addressable loops are used to:

A. Increase loop current
B. Localize shorts so the rest of the loop continues to operate ✓
C. Convert Class B to Class A
D. Power NA Cs

Localize shorts so the rest of the loop continues to operate

Definition: Isolators segment faults to improve survivability of "SLC" pathways. Reference: "NFPA" 72 (2022) Circuits and Pathways.

Approved Page 0

Point text at the panel/annunciator should:

A. Use generic names only
B. Match the drawings with clear locations and functions ✓
C. Show addresses only
D. Not be displayed

Match the drawings with clear locations and functions

Definition: Clear, consistent labeling speeds response and reduces errors. Reference: "NFPA" 72 (2022) Documentation and Annunciation.

Approved Page 0

Where should the end of line resistor be installed on a Class B initiating circuit?

A. Inside the panel
B. At the first device
C. At the last device on the run ✓
D. Not required

At the last device on the run

Definition: Placing "EOL" at the last device supervises the entire circuit for opens/grounds. Reference: "NFPA" 72 (2022) Circuits and Pathways.

Approved Page 0

Which networked pathway classification applies to supervised Ethernet "IP" fire alarm transport?

A. Class A
B. Class B
C. Class N ✓
D. Class C

Class N

Definition: Class N provides requirements for supervised network pathways. Reference: "NFPA" 72 (2022) Chapter on Pathway Classifications.

Approved Page 0

Which pathway class uses a return path so a single open does not isolate devices?

A. Class A ✓
B. Class B
C. Class N
D. Class E

Class A

Definition: Class A includes a redundant return path to maintain continuity around a single break. Reference: "NFPA" 72 (2022) Circuits and Pathways.

Approved Page 0

What is a common nominal starting spacing for spot smoke detectors on smooth ceilings (subject to listing)?

A. 20 feet
B. 30 feet ✓
C. 40 feet
D. No nominal spacing exists

30 feet

Definition: Thirty feet nominal is a typical design starting point; always follow the device listing and room features. Reference: "NFPA" 72 (2022) Initiating Devices.

Approved Page 0

Corridor smoke detector spacing for corridors up to about 10 feet wide is often:

A. Every 15 feet
B. Every 30 feet
C. About every 41 feet on center ✓
D. No limit

About every 41 feet on center

Definition: Corridor rules allow wider spacing than open areas due to channeling; verify with code and listings. Reference: "NFPA" 72 (2022) Initiating Devices.

Approved Page 0

If multiple supplies feed strobes visible together, you must:

A. Do nothing
B. Ensure listed synchronization so flashes align ✓
C. Set different flash rates
D. Turn off corridor strobes

Ensure listed synchronization so flashes align

Definition: Visible appliances in the same field of view must flash in sync to avoid disorientation. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

Public mode visible notification candela is chosen by:

A. Installer preference
B. Using tables based on room size and mounting height ✓
C. Fixed 15 candela everywhere
D. Only by trial

Using tables based on room size and mounting height

Definition: Use listed candela tables and mounting height to assure visibility. Reference: "NFPA" 72 (2022) Chapter 18.

Approved Page 0

Combination fire and carbon monoxide systems must provide:

A. Same tones for both
B. Distinct tones/patterns and indicators for each hazard ✓
C. Visible only
D. Voice only

Distinct tones/patterns and indicators for each hazard

Definition: Provide distinct patterns (e.g., T 3 fire, T 4 carbon monoxide) and labeling so occupants take correct actions. Reference: "NFPA" 72 (2022) Notification.

Approved Page 0

Which cable types are listed for power limited fire alarm circuits per "NEC" Article 760?

A. THHN only
B. NMB only
C. FPL, FPLR, FPLP ✓
D. CL 2 only

FPL, FPLR, FPLP

Definition: Use listed fire alarm cables: FPL (general), FPLR (riser), and FPLP (plenum). Reference: "NEC" 70 (2020) Article 760.

Approved Page 0

Which cable can be installed in environmental air plenums without added raceway when per listing?

A. FPL
B. FPLR
C. FPLP ✓
D. Any low voltage cable

FPLP

Definition: FPLP is plenum rated; otherwise place lower ratings in suitable raceways. Reference: "NEC" 70 (2020) Article 760.

← Previous Page 9 of 24 Next →